Kunshan Plant · Jiangsu  |  Hefei Plant · Anhui, China [email protected]  |  WhatsApp +86 132 6227 6239
C-BOX Electronic Technology Request a Quote
Home  ›  Products  ›  Power Distribution Units (PDU)

Product line 04 / 12 · Power Distribution

Power Distribution Units (PDU)

One 3U panel that feeds the whole rack: nine 220 VAC outlets, conditioned +5 / +12 / −12 / +24 VDC rails, load switch, circuit breaker and emergency stop — engineered as a 19″ module, not an afterthought.

C-BOX 3U rack PDU, finned aluminium chassis with load switch, dual circuit breaker, emergency stop and nine 220 VAC outlets

Overview

C-BOX builds power distribution as a proper rack module. Our 3U PDU houses everything the electrical side of a system needs in one finned 481 × 482.7 × 132.9 mm chassis: a load switch with OFF-position locking, a double-pole circuit breaker, an emergency stop and nine fuse-protected 220 VAC outlets — plus a conditioned low-voltage section delivering +5 V, +12 V, −12 V and +24 V rails for the electronics in the rack. The low-voltage-controls-high-voltage circuit concept keeps the operator side safe, and every unit is wired, labelled and function-tested in our workshop before it ships. 1U and 2U variants and custom outlet mixes are built to order.

  • 3U · 19″ · 481 × 482.7 × 132.9 mm, cooling fins on both sides
  • 9 × AC 220 V outlets, AC throughput ≥ 3500 W
  • Conditioned DC rails: +5 V · +12 V · −12 V · +24 V
  • Load switch with OFF lock + double-pole circuit breaker
  • Emergency stop, power ON/OFF and fuse on the front panel
  • Low-voltage-controlled high-voltage circuit design
  • C19 16 A input · 115 / 250 VAC · 50 / 60 Hz · −20…+60 °C

Request a quote for this line

Typical specifications

Height3U (1U / 2U variants on request)
Dimensions481 × 482.7 × 132.9 mm, side cooling fins
InputC19 16 A · 115 / 250 VAC · 50 / 60 Hz
AC outputs9 × 220 VAC, ≥ 3500 W total
DC outputs+5 V ≥ 32.5 W · ±12 V ≥ 120 W · +24 V ≥ 240 W
Front panelload switch (OFF lock) · double-pole MCB · e-stop · fuse · status LEDs
Environment−20…+60 °C operating · −40…+65 °C storage
Weightapprox. 9.05 kg

Power distribution & system units — all 2 part numbers

Same interface dimensions as the nVent SCHROFF equivalents — our own tooling, material and finish.

Every model has its own page with specifications and RFQ. Use your browser search (Ctrl/Cmd+F) on this page, or send us the number and we will quote it.

PDU (2)

13100-141 · 13100141
PSU 19" for CompactPCI, AC/DC, 3 U, 8 HP
24563-100 · 24563100
EuropacPRO 19" Subrack Kit for Power Distribution Module, Unshielded, 3 U, 84 HP, 115 mm

PDU architecture: input, protection, outlets and DC rails

A rack PDU is a distribution board in 19″ format. What matters is not the outlet count on the front but the input rating, the protection device upstream, and whether the outlets are grouped the way the load is grouped.

ElementWhat to specifyWhy it decides the part
Inputsingle-phase 230 V or three-phase, cable length and plug typethe plug and cable are usually the longest lead item
ProtectionMCB per group, curve B or C, RCD if required by site rulesa 16 A group should not be loaded above about 80% continuously
OutletsIEC C13 / C19 count and groupinggroup by equipment pair, not by physical position, so one trip does not take both feeds
Meteringper-PDU or per-outlet, local displayper-outlet metering is what makes capacity planning possible
DC railsvoltages, current per rail, isolationa PDU with DC rails is a power supply as well as a distributor
Mounting3 U horizontal, or vertical zero-Uhorizontal takes rack height, vertical takes depth beside the rails

Load, derating and heat inside the rack

A PDU dissipates heat like any other equipment: a 3 kW loaded PDU with 98% efficiency puts roughly 60 W into the rack air. That is small against a full rack but not negligible in a closed cabinet, and it is why PDUs are usually mounted low, where the intake air is coolest. Continuous loading above 80% of the breaker rating shortens the breaker life and, in a warm rack, causes nuisance trips.

Earthing and isolation

For anything with a metal chassis and a mains input, the earth path is part of the product, not an installation detail: the PDU frame must bond to the cabinet, and the cabinet to the building earth, with a measurable low-resistance path. If the site requires an RCD, state the residual current and whether it is per-PDU or per-rack — it changes the input assembly.

What a PDU enquiry should contain

Applications

Where this product line is typically used.

Test & measurement racksOne panel feeds and protects a whole instrument stack.
Industrial control cabinetsSwitching, protection and e-stop in a single 3U module.
Communication systemsConditioned 24 / 12 / 5 VDC rails for radio and network gear.
OEM equipmentPDUs designed around your machine's electrical concept.

Related product lines

Parts that usually go together with Power Distribution Units (PDU).

Related categories

Continue with

Load, rails and variants

What load can the 3U PDU carry?

Nine AC 220 V outlets with AC throughput of at least 3500 W, on a C19 16 A input, 115 / 250 VAC, 50 / 60 Hz, rated -20 to +60 C. The chassis is 481 x 482.7 x 132.9 mm with cooling fins on both sides.

What are the low-voltage rails for?

+5 V, +12 V, -12 V and +24 V rails feed the electronics inside the rack. The low-voltage-controls-high-voltage design keeps the operator side safe, and every unit is wired, labelled and function-tested before shipment.

Can the outlet mix be changed?

Yes. 1U and 2U variants and custom outlet mixes are built to order, with load switch and OFF-position locking, double-pole breaker and emergency stop on the front panel.

Made in our own plants — chassis and precision parts from Kunshan, cabinets and surface finishing from Hefei: CNC punching, press braking, CNC machining, assembly, inspection and export packing in-house.

Kunshan plant →Hefei plant →

Send us the part number or drawing.

Cross-referencing against major international 19″ system part numbers is our daily routine — we quote within 24 hours for standard items.

Request a Quote

Compatibility

Every part below follows the same interface dimensions as the standard 19″ subrack system, so it fits existing installations without rework. If your drawing or BOM lists an 8-digit order number, send it over — we will confirm the equivalent C-BOX part, lead time and price.

Dimensionally compatible with nVent SCHROFF parts under the same order numbers — including 34560-084, 34561-584 and 24560-235. A direct replacement, same interface dimensions. Browse all 127 model pages →